Room air conditioners.
CFR · 2024-01-01 · US · Title 10
(a) (2) For each basic model of room air conditioners, a sample of sufficient size shall be randomly selected and tested to ensure that— (i) Any represented value of estimated annual operating cost, energy consumption or other measure of energy consumption of a basic model for which consumers would favor lower values shall be greater than or equal to the higher of: (A) The mean of the sample, where: (B) The upper 97 (ii) Any represented value of the combined energy efficiency ratio (CEER) (determined in § 430.23(f)(3) for each unit in the sample) or other measure of energy consumption of a basic model for which consumers would favor higher values shall be less than or equal to the lower of: (A) The mean of the sample, where: (B) The lower 97 (3) The cooling capacity of a basic model is the mean of the measured cooling capacities for each tested unit of the basic model, as determined in § 430.23(f)(1) of this chapter. Round the cooling capacity value to the nearest hundred. (4) The electrical power input of a basic model is the mean of the measured electrical power inputs for each tested unit of the basic model, as determined in § 430.23(f)(2) of this chapter. Round the electrical power input to the nearest ten. (5) Round the value of CEER for a basic model to one decimal place. (b) (2) Pursuant to § 429.12(b)(13), a certification report shall include the following public product-specific information: The combined energy efficiency ratio in British thermal units per Watt-hour