Distribution transformers.
CFR · 2024-01-01 · US · Title 10
(a) (2) For each basic model of distribution transformer, efficiency must be determined either by testing, in accordance with § 431.193 and the provisions of this section, or by application of an AEDM that meets the requirements of § 429.70 and the provisions of this section. (i) For each basic model selected for testing: (A) If the manufacturer produces five or fewer units of a basic model over 6 months, each unit must be tested. A manufacturer may not use a basic model with a sample size of fewer than five units to substantiate an AEDM pursuant to § 429.70. (B) If the manufacturer produces more than five units over 6 months, a sample of at least five units must be selected and tested. (ii) Any represented value of efficiency of a basic model must satisfy the condition: (b) (2) Pursuant to § 429.12(b)(13), a certification report shall include the following public product-specific information: For the most and least efficient basic models within each “kVA grouping” for which part 431 prescribes an efficiency standard, the kVA rating, the insulation type ( (c) (d)