The simulation tool.
CFR · 2024-01-01 · US · Title 10
521.1 Annual energy consumption shall be simulated with a multi-zone, 8760 hours per year building energy model. The model shall account for: 521.1.1 The dynamic heat transfer of the building envelope such as solar and internal gains; 521.1.2 Equipment efficiencies as a function of load and climate; 521.1.3 Lighting and HVAC system controls and distribution systems by simulating the whole building; 521.1.4 The operating schedule of the building including night setback during various times of the year; and 521.1.5 Energy consumption information at a level necessary to determine the Energy Cost Budget and Design Energy Cost through the appropriate utility rate schedules. 521.1.6 While the simulation tool should simulate an entire year on an hour by hour basis (8760 hours), programs that approximate this dynamic analysis procedure and provide equivalent results are acceptable. 521.1.7 Simulation tools shall be selected for their ability to simulate accurately the relevant features of the building in question, as shown in the tool's documentation. For example, a single-zone model shall not be used to simulate a large, multi-zone building, and a steady-state model such as the degree-day method shall not be used to simulate buildings when equipment efficiency or performance is significantly affected by the dynamic patterns of 521.1.8 All simulation tools shall use scientifically justifiable documented techniques and procedures for modeling building loads, systems, and equipment. Th
official document · source cfr-2024 · id 10:§ 434.521